Estimated HVAC Equipment Service Life

This detail is taken from the ASHRAE expectancy equipment chart for HVAC equipment service life information in median years for Engineering staff. If you will review this information then you can understand the estimated HVAC equipment lift which will be useful for your design, installation, or maintenance work planning. Here each HVAC equipment shall be presented in picture form as well as video form for easy understanding. Let us start…

Window AC Unit’s median life 10 years
Residential-Single or Split Package AC’s median life 15 years
Commercial Through The Wall AC’s median life 15 years
Water Cooled Package AC’s median life 15 years
Residential Air To AIr Heat Pump’s median life 15 years
Commercial Air To Air Heat Pump’s median life 15 years
Commercial Watr To AIr Heat Pump’s median 19 years
SIngle Zone Roof Top AC’s median life 15 years
Multi Zone Roof Top AC’s median life 15 years
Reciprocating Package Chiller’s median life 20 years
Centrifugal Package Chiller’s median life 23 years
Absorption Package Chiller’s median life 23 years
Galvanized Metal Cooling Tower’s median life 20 years
Wood Cooling Tower’s median life 20 years
Ceramic Cooling Tower’s median life 34 years
AIr Handling Unit’s median life 20 to 25 years
Fan Coil Unit’s median life 20 years
Air Washer’s median life 17 years
Coils, Condenser, Evaporator’s median life 20 years
Shell and Tube Heat Exchanger’s median life 24 years
Reciprocating Compressor’s median life 20 years
Duct Work median life 30 years
Blanket Insulation median life 24 years
Dampers’ median life 20 years
Diffusers, Grills, and Registers’ median life 27 years
VAV and Double Duct Boxes’ median life 20 years
Centrifugal Fans’ median life 25 years
Propeller Fans’ median life 15 years
Axial Fans’ median life 20 years
Ventilating Roof Top Fans’ median life 20 years
HVAC Pipes’ media life 50 to 100 years
Valves and Actuators’ median life 10 to 20 years
Base Mounted Pump’s median life is 20 years
Pipe Mounted Pump’s median life is 10 years
Sump and Well Pump’s median life is 10 years
Condensate Pump’s median life is 10 years
Electric Motors’ median life is 18 years
Electric Breakers’ median life is 17 years
Electric Transformer’s median life is 30 years
Pneumatic, Electric, and Electronic Controls’ median life is 15 to 20 years
Steam Turbines’ median life is 30 years
Boiler Hot water and Steam Steel Water-Tube’s median life is 24 to 30 years

Boiler Hot Water and Steam Fire-Tube’s median life is 25 years

Boiler Hot water and Steam Cast Iron’s median life is 30 to 35 years
Boiler Hot water and Steam Electric’s median life is 15 years
Unit Heaters Electric and Gas’ median life is 13 years
Radiant Heater Electric median life is 10 years
Radiant Heater Hot Water or Steam’s median life is 25 years